T90 Copper
Single copper conductor with thin wall PVC insulation and Nylon covering. Rated 600 Volts, and FT1.
Applications
- General purpose building wire for installation as exposed or concealed wiring and in raceways (except cable troughs) in dry locations.
- Minimum recommended installation temperature minus 10°C.
- Maximum conductor temperature 90°C dry, 75°C in wet locations, and 60°C when exposed to oil.
- Approved for use with ceiling fixtures.

Specifications & Compliances
- CSA C22.2 No. 75-M1983
- T90/TWN75 is NOT sunlight resistant.
- For 3-wire 120/240 and 120/208V residential services or sub-services, the allowable ampacity for 2/0awg copper shall be 200 Amperes. In these cases, the 5% adjustment per CE Code Rule 8-106(1) cannot be applied.
- The above is based on not more than 3 copper conductors in raceway or cable.